04
What the twin found
Each entry of the twin's findings log is a fault found before any hardware existed, in the plant design or in the twin itself. Here are 12 examples and the count by group.
The 436 log entries by group
436 log entries, 419 of them plant faults found by the twin. Counted from the kind line of each entry.
| PLC logic: drivers, resets, sequences, deadlocks | 129 |
| Safety wiring, safety functions and safety design | 92 |
| Dimensions and mechanics | 74 |
| Signals, terminals and timing | 71 |
| Device data, order codes and drive settings | 45 |
| Faults of the twin's own models and test tools | 17 |
| Design, lists and mounting | 8 |
What the twin found
Examples from the log
4 examples: signals and devices
- Inverted sensor output. The teach in the checklist would switch a presence output the wrong way, so the machine would react to an empty place. The checklist is fixed, which saves a search on site.
- Current too low. A drive's safe stop input draws 9.7 mA, but the safe output needs 20 mA to watch its load. On site the safety group would stop and the feeder never start, on every machine with this drive.
- Timeout too short. A level sensor needs up to 5 s to start, the port waited 2 s. Every power-up would end in a port error and a manual reset.
- Wrong order code. The drives were ordered with the adapter of another fieldbus, so none of them would talk to the PLC. That saves 1 to 3 weeks of waiting for new adapters.
5 examples: safety
- No feedback. The cart's safety logic never checked that safe torque off had switched off. A cross-circuit would stay hidden; now it blocks the restart.
- 24 V into 230 V. A 24 V safety output was planned straight into the 230 V stop circuit of the lift. Two safety contactors with feedback replace it.
- Reset starts motion. A reset would have started the robot program. Reset and start are now separate.
- Stopping time. A scanner field assumed a 0.3 s stop, but the conveyors coast for 3.22 s. The field would need 6.5 m; the conveyors get a safe brake.
- Muting too wide. A dock light curtain was muted while a rack stood waiting, so a hand beside it was not seen.
3 examples: logic, power and mechanics
- Deadlock. A ladle docked under a furnace with no room for the next tap held the whole melting line. A recovery path now takes the ladle away.
- Bus power. Six terminal rows drew more than the 2 A of their bus coupler. The build tool now sums the current of every station.
- 6 mm too high. The weigh idler of a belt scale stood 6 mm above its neighbours, where 0.8 mm is allowed. The scale would drift with the belt tension; shims fix it.